Text Box: UV Flame Detector
Text Box: ROBUST - Designed specifically for lifeboat institute type applications.
FAST RESPONSE - Typically detects flame in engine rooms / compartments in 2 secs.
EASY TO INSTALL - Provides simple volt free relay  outputs.
WIDE FIELD OF VIEW  - Up to 120° FOV provides wide coverage.              
ANTI VIBRATION MOUNTINGS  - (not shown) Assist in absorbing vibration and shocks    
Text Box: The Model 301LI ultraviolet (UV) Flame Detector has been developed from the well tried and proven Model 301.  The major difference is the  robust enclosure (housing) with ingress protection to IP65 and anti vibration mountings.   For additional protection, The electronics are conformally coated. 

On completion, each unit is continuously tested for a period of seven days prior to despatch to ensure there is no component failure during that time (such failures normally occur wthin the first 24 hours).   Percentage tests are also carried out for water ingress (IP65) and vibration.

As with all UV Flame Detectors, avoid spurious sources of UV such as sparks, quartz halogen lights (not covered by glass), lightning etc.

MAINTENANCE
Gently clean the sensor tube with lint free cloth and alcohol.   Ensure sensor tube is kept free from oil, grease and silicones.   Functionally test the detector with Intronics UV Flame Simulator weekly.
Text Box: SPECTRAL RESPONSE              185 - 260nm.
FOV (FIELD OF VIEW)                 up to 120 degrees.
OPERATING VOLTAGE               12-30Vdc.
POWER (TYPICAL) AT 25Vdc:
  Fault relay ON   - Quiescent 18mA. - Alarm 31mA.
  Fault relay OFF -         ‘’         8mA.   -   ‘’     22mA.  

INGRESS PROTECTION               to IP65

OPERATING TEMPERATURE      -10° to +60°C

RESPONSE TIME            Typically from  2 seconds
                                         depending on type of fuel, 
                                         size of flame and distance.

WEIGHT UNPACKED     1kg with anti vib. mountings

SPECIFICATION

APPLICATIONS

Lifeboat engine rooms / compartments and similar harsh applications free from oil mist, oil spray and spurious sources of UV.  The Model 302LI IR Flame Detector (under development) should be used if any of the above problems exist.

Model 301LI

As used on UK Lifeboats

Text Box: This Flame Detector is just one of a comprehensive range which can be seen on our website.   Alternatively, if you have an unusual application requiring a non standard detector, please contact us. 